W41H1: HA control layer: safety guards + native (no-JS) dashboard

Design doc for locally driving the de-clouded Hisense AEH-W41H1 over Matter (via python-matter-server, HA 2026.6) with built-in Lovelace cards only and a correct set of safety guards. Produced by a 4-lens research fan-out (stock cloud plugin hisense_ac_plugin, our RS-485 driver, stock-FW/link RE docs 09/10, HA native-card docs) + adversarial verification.

Superseded by a shipped integration. The native unified dashboard/entity this doc designs toward now ships as integrations/hisense-unified-ac: a HACS custom integration (separate repo/submodule). Treat the YAML and tables below as reference for that integration rather than an open design; the feature/guard matrix (§1), the guard-ownership table (§2), and the dashboard YAML (§3) remain the load-bearing spec.

Three design facts this doc is built on, load-bearing for the tables below:

  • The firmware auto-powers-on on mode-select: matter_drivers.cpp:1035-1044: a non-off SystemMode write calls hisense_send_power(true) then hisense_flush_command() (mode frame), so climate.set_hvac_mode: cool already emits power-on-then-mode. HA does not own auto-power-on. The empirical “wrote SystemMode, unit stayed off” is a link-readiness issue (or the on-frame being ineffective from cold-off), a HW-verify item (P4), not an HA guard.
  • Native cards call climate.*/fan.* directly, so guard scripts placed in front of a write are unreachable. Guards can only be (a) firmware-side (power-on, setpoint-rides-with-mode, bus pacing) or (b) reactive automations that fire after the state change.
  • Specials (Eco/Turbo/Mute/Sleep) are not controllable from HA via the mfg cluster. matter-server write_attribute resolves ALL_ATTRIBUTES[cluster_id] (the CHIP registry); cluster 0xFFF1FC00 is absent → the write returns null/KeyError, not a real write. Its custom-cluster mechanism (custom_clusters.py) is read/poll only. This doc’s proposed fix was to re-expose specials via standard Matter Presets; what actually shipped is simpler, plain per-endpoint OnOff switches (ep3-6, see docs/07), which sidesteps the mfg-cluster write gap without touching Presets at all.

There is no atomic SystemMode+setpoint write in matter-server, no decoded power bit to read back, and SpeedCurrent/PercentCurrent/LocalTemperature are real Matter readbacks that update on their own (manual resync fights them). The native card uses the entity’s 16–32 AbsMin/Max, not a 16–30 clamp.


1. Feature matrix (validated inventory)

Command-side byte encodings are DI-tap-confirmed (reverse-engineering/docs/10 HIL chronology, Phase D) and survive the docs/10 §5 “ESPHome layout isn’t in stock FW” correction (that correction bites the status decode, not these command bytes). Values in the cloud column are STRING property writes.

HVAC modes

| Mode | Cloud t_work_mode | Our SystemMode → 0x65 byte18 | Auto-powers-on? | Temp settable | HA control | |—|—|—|—|—|—| | Off | "0" power (t_power:"0") | Off → literal OFF frame | n/a | – | native set_hvac_mode: off | | Cool | "2" | 3 → 0x50 | yes (firmware) | yes | native | | Heat | "1" | 4 → 0x30 | yes (firmware) | yes | native | | Dry | "3" | 8 → 0x70 | yes (firmware) | no | native | | Fan-only | "0" | 7 → 0x10 | yes (firmware) | no | native | | Auto | absent on window AC (0,1,2,3,5) | 1 → 0x90 (driver-reachable) | (would) | – | needs FeatureMap Auto bit (FW) | | E-star/eco | "5" (a mode, unmapped in HA) | ≈ mfg-Eco special (byte33 0x30) | assumed | – | none today; reconcile w/ mfg-Eco (open Q) |

Setpoint rides inside the mode 0x65 at byte19 (temp*2+1); a standalone OccupiedCooling/HeatingSetpoint write returns IM 0x86: the firmware already flushes setpoint in its own 0x65, so climate.set_temperature works when it lands with/after a mode. Temp is only honored in Cool/Heat (cloud strips it in dry/fan; our range is 16–32 on the wire, model spec 16–30).

Fan speeds (on the SEPARATE fan.test_product_3 entity)

SpeedSetting 1..6 → byte16 0x03/0x0B/0x0D/0x0F/0x11/0x13 (quiet…high; 0x03 quiet is VERIFY). Cloud exposes only 3 (t_fan_speed 5/7/9 = low/med/high). Conflict to resolve on HW: the live glue INTEGRATION.md:127,237 maps PercentSetting through mapPercentToMode() into ~4 buckets (off/low/med/high), not the 6-step percent_to_hisense_fan(): so the fan-speed slider may yield 4 buckets, not 6. Fan never auto-powers-on; fan is not settable in Dry; 0% sends AUTO fan, not off.

Special functions

Byte-level mfg-cluster encodings (attr IDs ↔ RS-485 command bytes) and the CompressorHz/OutdoorTemp telemetry-gap status are owned by docs/01, not repeated here; this table only adds the HA-facing columns (cloud mapping, interlocks, reachability).

Special Cloud Our path (mfg cluster) Interlocks (per driver) HA today
Turbo t_super mfg 0x0001 XOR Eco (shared byte33); forces fan-high + 16 °C not reachable (mfg write broken)
Mute/Quiet t_fan_mute mfg 0x0002 forces fan quiet; independent of byte33 (so it fights Turbo’s fan-high) not reachable
Eco/E-star t_work_mode:"5" mfg 0x0000 XOR Turbo; turn-off may not clear on HW not reachable
Sleep none on window AC mfg 0x0003 forces fan-low not reachable
Swing V/H none RockSetting bits (fan cluster, not mfg) H-swing command unvalidated native fan.oscillate = one collapsed toggle

Cloud-only, absent on our hardware (drop): ac_purify/health (status bit always 0), ac_8heat, ac_ai, ac_dr, ac_humidity, 8-position/follow-me swing, self-clean.


2. Guards: where each actually lives (corrected)

# Guard Owner Status
G1 Mode-select powers the unit on Firmware (matter_drivers.cpp:177-180) already done; verify on HW (P4): the empirical cold-off failure is the open risk
G2 Setpoint rides with the mode frame (no bare 0x86 write) Firmware (flushes setpoint in its own 0x65) done; HA should still prefer set_temperature with hvac_mode so a mode is present
G3 Half-duplex pacing / ~1 Hz transaction Firmware bus task (send→listen ≤500 ms) done; HA adds a light slider debounce (≥1.5 s) only as courtesy, cloud uses 3 s cmd-cache + 10 s switch-debounce, so lean generous
G4 Link-ready gate (don’t command before DevType/0x07 handshake) HA reactive template binary_sensor.ac_link = LocalTemperature is live; surface it; optionally block special/automation writes on it. (This is a link signal, not a power signal, there is no power readback.)
G5 Reconnect resync after A/C-initiated reset/OTA/reconfig HA automation on climate unavailable→available, re-send last mode/setpoint from input_* mirrors; do not fight a reconfig
G6 Special-function interlocks (Eco⊕Turbo, mode-restrict, forced fan) Firmware (once specials move to standard Matter) deferred with the specials; today unreachable so moot
Temp/fan validity per mode (no temp in dry/fan; no fan in dry) Firmware should reject; HA card can’t clamp verify HA card behavior on HW; if the card leaves temp dialable in dry, add a reactive automation that reverts it

Key point: no imperative guard scripts sit in front of the native cards (they can’t). The firmware is the enforcement layer; HA contributes G4 (link awareness) and G5 (reconnect resync) as reactive automations, plus optional slider debounce.


3. Native (no-JS) dashboard

Two entities stitched with built-in cards (the climate entity has no fan_mode/swing_mode attrs, so climate-fan-modes/climate-swing-modes features render empty, fan+swing come from the fan tile). Feature strings are hyphenated (current docs).

type: vertical-stack
cards:
  - type: heading
    heading: Living Room A/C

  - type: thermostat
    entity: climate.test_product_3          # rename to climate.living_room_ac
    features:
      - type: target-temperature
      - type: climate-hvac-modes
        hvac_modes: [off, cool, heat, dry, fan_only]   # +auto once the FW FeatureMap bit lands

  - type: tile
    entity: fan.test_product_3
    name: Fan
    features_position: inline
    features:
      - type: fan-speed        # slider (may resolve to ~4 buckets via mapPercentToMode — verify)
      - type: fan-oscillate    # swing (V+H collapsed into one toggle)

  - type: tile                 # explicit power, since there's no decoded power readback on the dial
    entity: switch.test_product_power_3
    name: Power

  # Link/health chip so the user knows when the bus is actually up:
  - type: tile
    entity: binary_sensor.ac_link
    name: A/C link

Specials are intentionally absent until the firmware exposes them via standard Matter, a matter_write template switch for the mfg cluster does not work (see §0.3). When Sleep/Eco become Thermostat Presets, add a climate-preset-modes feature to the thermostat card (native); Quiet is already a fan speed; Turbo becomes a preset or a boost.

The Humidity endpoint was dropped (never fed, W41H1 status humidity isn’t mapped); ep2 is now outdoor temperature and ep8 is coil temperature, both fed and HA-readable, so tiles for those two are fine to add.


4. Phased plan

P3(a) partially overtaken: the current .zap already ships Thermostat FeatureMap 35 (Heat+Cool+Auto), so the fielded firmware doesn’t match this table’s “TODO” framing there. P3(b) went a different way too: specials shipped as plain per-endpoint OnOff switches (ep3-6, see docs/07’s parity matrix) rather than Presets, simpler and needing no HA-side SINGLE_SETPOINT_DEVICES/deadband handling. Table kept below for the reasoning, not as a live TODO.

Phase Deliverable HW-on needed?
P0 Rename device → “Living Room AC” (HA device registry; NodeLabel write doesn’t persist). Remove the JS climate-cluster-card dashboard + resource (pivot to native). no
P1 Native vertical-stack dashboard (§3): thermostat + fan tile + power tile. binary_sensor.ac_link template. no (renders + fires)
P2 Reactive automations: G5 reconnect-resync (last mode/setpoint mirrors via input_*); optional G4 link-gate + notification; optional fan-slider debounce. authoring no; validating yes
P3 (firmware/OTA) (a) Thermostat Auto FeatureMap 3 → 35 (0x23 = kHeating|kCooling|kAutoMode, shipped): HA lists us in SINGLE_SETPOINT_DEVICES (via matter_extra_hvac_modes) so Auto renders as a single-setpoint mode, consider the MinSetpointDeadBand (thermostat 0x19) companion if CHIP/device complains → auto renders. (b) Re-expose specials via standard Matter: Sleep/Eco as Thermostat Presets (kPresets + populate Presets/PresetTypes), Turbo as a preset/boost, retire the mfg-cluster control surface for HA (not taken, see note above). (c) Wire explicit eco-off (HISENSE_FEATURE_ECO_OFF, byte33 0x10, via hisense_apply_eco())/turbo-off/display-off frames. Rebuild + serial-bump + OTA (proven pipeline). reflash + verify
P4 (HIL) With the A/C on + linked: confirm mode-select really powers on from cold-off (the empirical failure), setpoint (no 0x86), fan slider bucket count (4 vs 6), swing, and (once P3 lands) presets. Confirm the LocalTemperature-live link proxy tracks the real handshake. yes

5. Open questions to settle on hardware

  1. Cold-off power-on: does an explicit on-frame actually power a physically-off unit? (empirical failure; firmware already sends it, so this is an on-frame/link question, not an HA one).
  2. Fan slider granularity: 6-step (percent_to_hisense_fan) vs ~4-bucket (mapPercentToMode), which does the live glue use? Reconcile the two source mappings.
  3. Temp visibility in dry/fan: does HA’s Matter climate card auto-hide set_temperature when the entity is in dry/fan, or stay dialable? (Matter advertises setpoints unconditionally.)
  4. OnOff vs SystemMode display: with OnOff=0 while SystemMode=Cool, does the climate entity show OFF or “cool”? (HA shows off when the OnOff switch is off, confirm.)
  5. Presets feasibility. Moot: specials shipped as plain OnOff switches.
  6. Do specials auto-clear on mode-change/power-off, and are Turbo/Mute truly exclusive (they use different frames, so their forced fan states fight)?
  7. Sleep enum cardinality + wire type (on/off vs 5-value) and eco-off/turbo-off actually clearing on HW (only the 0x04 baseline is wired today).

Grounding: workflow hisense-ac-control-research (4-lens fan-out + adversarial verify + completeness critic), reconciled with live matter-server/HA checks. Command byte offsets are DI-tap-validated per reverse-engineering/docs/03 (protocol) + docs/10 HIL chronology. This doc supersedes the JS-card direction.


Dashboard card + automation examples (#22)

Copy-paste starting points, wired to a renamed node’s entity IDs (e.g. a device you renamed to living_room_ac). A second, un-renamed node keeps the un-suffixed auto IDs (climate.test_product, switch.test_product_switch_3, …). Matter auto-names are ugly, rename in Settings → Devices → Entities and the IDs stabilize. Vertical swing is exposed as fan oscillation on the fan.* entity (FanControl Rocking → fan.oscillate); the panel Display is a plain switch (write-only, the A/C reports no display state back).

Lovelace view

type: vertical-stack
cards:
  - type: thermostat
    entity: climate.test_product_2          # mode / setpoint / fan
    name: Living Room A/C
  - type: entities
    title: Modes & fan
    entities:
      - entity: fan.test_product_2          # fan speed + Swing (oscillate)
        name: Fan / Swing
      - entity: select.test_product_sleep_2
        name: Sleep profile
      - entity: switch.test_product_switch_3_2
        name: Eco
      - entity: switch.test_product_switch_4_2
        name: Quiet
      - entity: switch.test_product_switch_5_2
        name: Turbo
      - entity: switch.living_room_living_room_ac_switch_display
        name: Panel display
  - type: glance
    title: Telemetry
    columns: 3
    entities:
      - { entity: sensor.test_product_power_climate,   name: Power }
      - { entity: sensor.test_product_voltage_2,       name: Voltage }
      - { entity: sensor.test_product_active_current_2, name: Current }
      - { entity: sensor.living_room_living_room_ac_temperature_outdoor, name: Outdoor }
      - { entity: sensor.living_room_living_room_ac_temperature_coil,    name: Coil }
      - { entity: binary_sensor.test_product_door,     name: Aux heat }
  - type: gauge
    entity: sensor.test_product_power_climate
    name: A/C power
    unit: W
    min: 0
    max: 1500
    severity: { green: 0, yellow: 800, red: 1200 }

Automations

# 1) Auto-Eco when the A/C draws a lot (curb peak power)
- alias: "A/C: Eco when power high"
  trigger:
    - platform: numeric_state
      entity_id: sensor.test_product_power_climate
      above: 900
      for: "00:02:00"
  condition:
    - condition: state
      entity_id: switch.test_product_switch_3_2
      state: "off"
  action:
    - service: switch.turn_on
      target: { entity_id: switch.test_product_switch_3_2 }

# 2) Sleep profile + dim the panel at bedtime (only if the A/C is running)
- alias: "A/C: Sleep at bedtime"
  trigger:
    - platform: time
      at: "23:00:00"
  condition:
    - condition: not
      conditions:
        - condition: state
          entity_id: climate.test_product_2
          state: "off"
  action:
    - service: select.select_option
      target: { entity_id: select.test_product_sleep_2 }
      data: { option: "General" }
    - service: switch.turn_off
      target: { entity_id: switch.living_room_living_room_ac_switch_display }

# 3) Swing on while cooling (even airflow)
- alias: "A/C: Swing while cooling"
  trigger:
    - platform: state
      entity_id: climate.test_product_2
      to: "cool"
  action:
    - service: fan.oscillate
      target: { entity_id: fan.test_product_2 }
      data: { oscillating: true }

# 4) Panel display back on in the morning
- alias: "A/C: Display on in the morning"
  trigger:
    - platform: time
      at: "07:00:00"
  action:
    - service: switch.turn_on
      target: { entity_id: switch.living_room_living_room_ac_switch_display }