09: Energy monitoring (Watts + kWh), like the cloud app

Goal: expose live power (W) and cumulative energy (kWh) for the A/C, native to Home Assistant’s Energy Dashboard, matching what the Hisense cloud shows, but computed locally from the RS-485 telemetry we already decode.

0. How the cloud actually does it (and what “accurate” means here)

These inverter splits almost never carry a revenue-grade meter. The cloud number is one of:

  • (a) a value the indoor MCU reports (it senses DC-bus / compressor current for inverter control), or
  • (b) a model: power estimated from compressor frequency + mode.

Our telemetry map (see INTEGRATION.md §telemetry, mapped 2026-07-07) suggests this unit does sense both voltage and current, so we can do real P = V·I rather than a pure model. Either way the figure is an estimate; one calibration pass against a plug-in meter makes it trustworthy (§4). The cloud’s is an estimate too, ours can be at least as good, and local.

1. What we already have (no new decode needed)

From the 3-state correlation (cool 60 Hz → off 0 Hz → heat 50 Hz):

Byte Field Confidence Use
@50 supply voltage (V) High, reads 218 V loaded / 222 V idle (sags under load), matches ~230 V mains V term
@55 (=@145) phase/bus current A Med, zeros when compressor off, tracks load candidate I
@56 (=@144) phase/bus current B Med candidate I / second leg
@60 active current / power reading Med candidate I
@42 compressor actual freq (Hz) Confirmed model input / cross-check
@41/@43 compressor target freq (Hz) Confirmed
@45 outdoor coil temp (°C) Confirmed (reverses cool/heat) diagnostic (COP/efficiency later)

Unknowns to resolve by calibration: the scale of the current byte(s) (raw → amps) and the power factor (inverter input PF is ~0.6–0.98 depending on load).

2. Power model: two paths, pick by what calibration shows

Path A, direct metering (preferred if it validates):

P_watts = (V=@50) × (I=k·@55) × PF

We likely have real V and I. Solve k (current scale) and PF from the calibration points. Most accurate, responds to real voltage sag, fan load, part-load PF.

Path B, frequency model (robust fallback):

P_watts = a·comp_freq(@42) + b·fan_level + P_standby

Fit a, b, P_standby from the same points. Doesn’t depend on trusting the current bytes; this is what most community inverter-A/C energy integrations use.

Shipped: Path A only (power_estimate.h, §4a). Path B was never implemented; there is no frequency-based sanity clamp on the current reading.

3. Matter exposure: shipped

ElectricalPowerMeasurement (0x0090) ships on ep1 (both AmebaZ2 and ESP32). The “hang it on ep1” fallback considered below is what got built, because a new device-type endpoint carries the same endpoint-add build risk already navigated for ep4-7. Feature set is kAlternatingCurrent only (single-phase); optional attributes are Ranges, Voltage, ActiveCurrent. ActivePower/Voltage/ActiveCurrent are fed from power_estimate.h each status poll, in the cluster’s native mW/mV/mA units, and read 0 while the unit is off (not used as a liveness signal). kWh comes from HA Riemann-summing the power sensor (§5), the acceptable alternative this doc already flagged. ElectricalEnergyMeasurement (0x0091, CumulativeEnergyImported) was never added.

Delegate/Instance mechanics (found 2026-07-07, still true): ElectricalPowerMeasurement is a Delegate/Instance-based cluster, not plain ember-RAM: the server reads Accuracy, NumberOfMeasurementTypes, and the values through a C++ Delegate, so exposure is not the .zap-attr + emberAfWriteAttribute pattern used for ep3-7. The shipped delegate lives at firmware/src/sdk-edits/ElectricalPowerMeasurementDelegate.{h,cpp} (adapted from CHIP’s energy-management-app reference) and is shared as-is by the ESP32 build (#include <ElectricalPowerMeasurementDelegate.h> in app_main.cpp).

Outdoor and coil temp now have a standard cluster too: TemperatureMeasurement on ep2 (outdoor) and ep8 (coil), see docs/01/docs/07. Compressor Hz remains without a standard cluster. It reads live today through the mfg-cluster raw attribute path, and the hisense-unified-ac HACS integration renders it as sensor.*_compressor_frequency (see docs/01/docs/14).

4. Calibration procedure: clamp meter

Reference instrument: a clamp ammeter on the A/C live conductor. Two sub-cases:

  • True-power clamp (reads W / PF / kWh): gives real W directly → best; calibrate P against it.
  • Current-only clamp (reads A): gives us the true input current → directly calibrates the @55 byte→amps scale. We then form apparent power S = V(@50)·I, and real power P = S·PF. This unit’s inverter almost certainly has active PFC → assume PF ≈ 0.95 (tunable); at deep part-load PF drops, so the freq-model (Path B) is the sanity clamp there.

⚠️ Safety: clamping the live conductor means accessing the mains lead into the A/C. Mains voltage, clamp around a single insulated conductor (never bare metal), power the readings from the A/C’s own supply, and if the terminal block isn’t safely reachable, clamp at the isolator/plug lead instead. Don’t open anything live you’re not comfortable with.

Steps (interactive, ~15 min):

  1. Restart decode_ac_frames.py logging while I mark boundaries.
  2. Hold ~4 states, read the clamp at each: off/standby, low-cool (~40 Hz), hard-cool/turbo (~69 Hz), heat (~50 Hz). Tell me the amps (and W/PF if the clamp shows them) at each; I diff the frame to pair your reading with @50/@55/@56/@60/@42.
  3. tools/fit_power.py (to be written) fits the @55→A scale (and Path-B coefficients) by least-squares.
  4. Bake coefficients into the firmware power_estimate.h. Optional later: expose them as writable mfg attrs so you can retune from chip-tool without a reflash.

4a. Calibration (physical-meter validated: PD3-63VA panel meter, L3)

Power model, from three timestamp-synced points (photo EXIF ↔ logger [HH:MM:SS]), A/C on L3, power = V · ΔI(L3−baseline) · PF(0.95):

Time L3 A ΔI (A/C) P (W) @55 @42 Hz
22:07:36 1.1 0.0 0 0 0
22:12:32 2.3 1.2 268 8 31
22:10:48 5.3 4.2 934 15 68

@55 is √power, not linear amps, a linear fit gives incompatible slopes (33 vs 62 W/count), but quadratic-through-origin fits both load points to <1 %:

P_watts ≈ 4.15 · @55²        (k = 4.15 W per count², PF 0.95 baked in)
  @55=8  -> 266 W (meter 268)   @55=15 -> 934 W (meter 934)

Derived current for transparency: I ≈ P/(V·PF) → @55=15 → 4.47 A (meter 4.2), @55=8 → 1.27 A (meter 1.2). @60 gives the same curve (~0.66·@60²) as a cross-check. Caveat: two non-zero points, the quadratic is strongly supported but a 4th steady point would bulletproof it (tap now removed, so deferred). Voltage term uses @50 (coarse ~220; the meter’s live 234–236 V says @50 reads ~6 % low, minor, since current dominates).

4b. Compute location: firmware

The driver computes P and publishes it via the standard ElectricalPowerMeasurement cluster (§3). HA reads it as-is, Energy-Dashboard-native. The calc lives in a pure, host-testable power_estimate.h (mirrors matter_aircon_map.h) so the model is unit-tested without hardware.

5. Energy accumulation (kWh): HA Riemann sum, not firmware

kWh is derived in HA from the power sensor via a Riemann-sum helper; HA’s long-term stats hold the history. No firmware integrator is wired up. power_estimate.h carries a pure, host-tested energy-integrator pair (hisense_energy_add/hisense_energy_mwh, test/test_matter_map.cpp: 166-167), but nothing calls it: there’s no ElectricalEnergyMeasurement cluster to publish CumulativeEnergyImported to (§3), and a live version would still need NVS persistence to survive a reboot.

6. Implementation phases

  • P1: Calibrate. Done, §4a: meter + 4-point capture, quadratic fit P ≈ 4.15·@55².
  • P2: Firmware compute. Done: power_estimate.h, pure and host-tested like matter_aircon_map.h.
  • P3: Matter wire. Done, on ep1 rather than a new endpoint (§3): ElectricalPowerMeasurement only, fed each downlink. No ElectricalEnergyMeasurement (§5).
  • P4: HA. Power sensor confirmed live; Energy Dashboard wiring is a per-installation HA step, not tracked here.
  • P5: Validate. Open: no recorded comparison against the cloud app’s numbers.